Vivace Process Instruments

Vivace Process Instruments

Cravinhos - SP, 14140-000, Brazil

Position Transmitter VTP10

Position Transmitter VTP10

Position Transmitter VTP10 helps to calculate the correct position for system at the time of installing, according to user calibration and configurations, exporting this measurement to digital communication Profibus-PA or HART (4-20mA). It is used to monitor linear or rotative movement systems such as valve actuators.

Linear or rotary applications: manual and modulating control valves, sluice gates, tilting systems, conveyor belt alignment, level measurement etc. It can be configured, calibrated and monitored by configurators and tools based on EDDL® or FDT/DTM® technologies, according to specific protocol.

The transmitter is easy to install and to initialize and it also offers environment temperature measurement and several predictive diagnostics to help system maintenance such as a position histogram and reversal, strokes and mileage counters. The measuring system has no mechanical contact with the system to be measured, since it works on magnetic field effect, in order to guarantee high precision and immunity to mechanical variations.

Benefits:
 

  • HART® 7 or Profibus-PA Communication Protocols
  • For linear and rotary applications: control, manual, modulator or sluice valves, tilting systems, alignment of conveyor belts, level measurement etc.
  • No Polarity Power Supply
  • Work Range Configuration
  • Operation Limits Alarms
  • No Mechanical Contact Magnetic Sensor
  • Remote Sensor (optional)
  • 5-digit, rotative, multifunctional, bargraph LCD
  • Predictive Maintenance Diagnostics
  • Position Histogram
  • Measuring Unit Configuration
  • Operation Temperature -40 to 85 °C
    • Supports EDDL and FDT/DTM Programmers and Tools
  • Local Adjust


 

  Technical Specifications:
 Power Supply  12-45 Vdc (HART) or 9-32 Vdc (Profibus-PA)
 Precision  ± 0.05% (Full Scale, considering non-linearity and histeresys effects)
 Certification  Explosion Proof and Intrinsically Safe (pending)
 Temperature Limits  - 40°C to 85°C
 Configuration  Local, EDDL, FDT/DTM, PALM and Android® Tools
 Indication  Display LCD 5-digits, rotative, multifunctional
 Mounting  On field, with bracket for 2" tube Remote sensor mounting (optional)
 Measure  Hall Effect Magnetic Sensor.
 Linear  0 to 100 mm / Rotative 0º to 120º (Minimum Span 10 mm or 5º)
 Housing Material  Aluminum
 Weight  1.5 Kg (without bracket)

 

Product Enquiry

SSL Secure Connection