D-32107 Bad Salzuflen GERMANY
Service intended
Electronic alarm sensor contacts are switches for tensions out a range of 10 - 30 V DC used for direct drive of a stored program system or other electronics. The signal output is instantaneous and analog to the movement of the instrument pointer. Liquid filling in the instrument is possible.
Technical Data
Contact arm bearing
Ruby stones
No. of contacts
Max. 4
Operating voltage
Ub = 10 ... 30 V DC, Residual ripple 10 %
Open circuit current
≤ 10 mA
Reverse battery protection
conditional on (Ub)
inductive protection
1 kV, 0,1 ms, 1k
Oscillator frequency
approx. 1000 kHz
Output type
PNP - make contact
Switching current
Imax ≤ 100 mA
Residual current
≤ 100 mA