Service intended:
Electromechanical alarm contacts are auxiliary contacts that make or break electric circuits. A sliding contact is a mechanical contact with a make/break capacity up to 10 W / 18 VA. The signal output is instantaneous and analog to the movement of the instrument pointer. Instruments with sliding contacts must be installed free from vibrations. Liquid-filling in the instruments is not feasible.
Technical Data
Contact arm bearing
Ruby stones
Material of contact points
AG 80 Ni 20
No. of contacts
Max. 4
Voltage
Min. Ueff : 24 V Max. Ueff : 250 V
Current rating
Make rating : 0,7 A
Break rating : 0,7 A
Continuous load : 0,6 A
Load
P min. : 0,4 W / 0,4 VA P max. : 10 W/ 18 VA
Accuracy
Approximately 0,5 % FS
Creep and air distances
To DIN VDE 0110 part 1 and 2 (degree of soiling: 3)
Voltage testing
To DIN VDE 0660 part 200
Circuit/earth connection: 2000 VAC 1 min.
Circuit/circuit: 2000 VAC 1 min.