XDI-F1
All Gas types Available
• Explosion proof
• Rugged and reliable
• CANbus / 4~20mA outputs
• Optional 2 alarm relays plus fault relay or 3 alarm relays
• Wide range of gas types / sensors
• Addressable or stand alone
• Hyper terminal communications / RS232 - live data and set up with 232 adapter
• One man calibration
• Data logging
The XDI-F1 Gas Sensor is capable of utilising a wide range of sensor cell types offering an unmatched number of gases that may be monitored. Standard 4~20mA signaling with CANbus address enables the sensors to be networked via the GDS Combi control system or customer preferred monitoring systems.
Specifications
Certification
Explosion proof ATEX IECEx
112G Exd IIC T6-T3 Gb
112D Extb IIIC T85˚C Db
Power Supply - 15 to 30vDC 24v nominal
Logging - Intervals - one minute to one hour
Storage - 2,880 readings
Outputs - 3 wire 4~20mA / 4 wire CANbus
Optional relays - Low alarm S.P.C.O / High alarm S.P.C.O / Fault alarm S.P.C.O
Inhibit option during servicing
Rating - 0.5A @30vDC
Housing Material - Copper free aluminium alloy, optional stainless steel
Finish - Chemical resistant epoxy paint / Optional - Marine grade finish
Sensor Material - Stainless steel 316S16
Ingress Protection - IP63 + weather shield IP65
Cable Entry - 2 x M20 - 1.5 pitch - alternatives 25mm - 3/4 NPT
Weight - 1.6kg
Temperature -15˚C to +55˚C
See certification for Exd use
Humidity - 0 to 99% RH non-condensing