Fusion Point, Ash Lane, Garforth, Leeds LS25 2GA, West Yorkshire, UK
All Gas Types Available
• Flexible output options
• Addressable or stand alone
• Hyper terminal communications rs232 line data and set up with 232 adapter
• Data logging
• Optional alarm relays
• Robust and weather-proof
The 30J enclosure has been designed to allow quick and easy access to its interior by adjustment of two allen screws, this factor is a major consideration when large system service and calibrations are being carried out. The detector is robust and weather-proof with improved response times due to the four mounting spacers allowing increased air movement around the detector these spacers also improve the mounting of the unit particularly on circular pillars typically found in carparks. S tandard 4~20mA signalling with CAN bus address enables the sensors to be networked via the GDS Combi control system or customer preferred monitoring system.
Specifications
Power Supply - 15 to 30vDC 24v nominal
Outputs
3 wire - 4~20mA
4 wire - CAN bus
Relays (optional)
Low alarm S .P.C.O
High alarm S .P.C.O
Fault alarm S .P.C.O / overrange
Rating 0.5A @30vDC
Inhibit option during servicing
Logging
Addressable sensors only
Intervals - one minute to one hour
Storage - 2,880 readings
Temperature: -15˚C to 55˚C
Humidity: 0˚C to 99% RH - non condensing
Sincerely Plantautomation Technology
Regards,
Client Success Team (CRM),