UNITRO-Fleischmann fault reporting systems

UNITRO-Fleischmann fault reporting systems

Gaildorfer Straße 15 D-71522 Backnang germany

Fault-alarm-STZ

Fault-alarm-STZ

STZ C3text

  • fault message center for max. 320
  • signal lines with LCD display,
  • printer connection, history

STZ fault

  • message centers fault message center with LED display,
  • optional UPS, telephone speech announcement
  • GSM / SMS, logging,
  • LON bus or TCP / IP connection

Mechanical design

  • Wall-mounted sheet steel housing RAL 7032 IP54
  • with aluminum door hinged right with cam lock
  • Indicators installed in recessed aluminum front panel
  • Fully wired with input and output terminals and SL rail below
  • Flange plate with Pg knockouts below

Function description STZ24

  • Fault reporting system according to ISA-18.1-1979 (R2004) and DIN 19235 4.2.1. Acknowledgeable new flashing fault message
  • Integrated mini-horn and operating button for the parameterization of idle working current control and response delay
  • per channel
  • Via LED labeling inset label
  • STZ24: decentral control via LON bus possible, with TCP / IP connection

Function description STZ C3text

  • Clear text message system in 24-level expandable via 2-wire LON bus FT
  • up to max. 320 messages, control decentralized up to 2 km distance
  • 4x 40 character LCD display with time, date and status
  • With integrated small horn and operating button for menu-driven parameterization of idle working current control , response delay and 64-channel output group message

Optional additional functions

  • Additional operating messages via two-color LED red / green (MB)
  • Uninterruptible power supply 230 / 24V battery buffered for up to approx. 10h mains failure
  • Automatic telephone dialer for voice announcement
  • SMS or fax remote alarm via GSM module
  • Intranet or Internet connection via MPCC1

Only STZ C3text

  • DCF radio clock synchronization
  • Logging via 58mm thermal paper built-in printer

Product Enquiry