Low Voltage Instrument Transformers M005585-I06
Low Voltage Instrument Transformers M005585-I06
The specified tightening torques are based on a dry assembly (coefficient of friction ȝ = 0,14), without the addition of lubricants!! If lubricants are provided, the torque has to be adjusted by the costumer.
1 . Secondary terminal cover, transparent, sealable
2 . Slot and hole to seal terminal cover
3 . Secondary terminal, brass nickel plated
4 . Secondary screw, galvanized steel, Phillips recessed head screw, max. 6mm ð (flexible)/10mm ð (solid), depending on the configuration M5, MA:3,5 Nm or M4, MA:2 Nm
5 . Cable protective cap
6 . Primary fixing device, Phillips recessed head screw, contact- safe, MA:0,5 Nm
7 . Option:Snap-on mounting bracket for hat rail acc. to DIN EN 60715-TH 35
8. Mounting feet
9 . Rating plate