Rhomberg Instruments

Rhomberg Instruments

Cnr Barlinka & Muscat Street Saxenburg Park Blackheath 7579 Cape Town South Africa

Vanguard Wireless Gas Detector

Vanguard Wireless Gas Detector

Vanguard Wireless Gas Detector

  • Operating Temperature: -40°F (-40°C) to 149°F (65°C)
  • Operating Humidity 0% to 98% RH recommended non-condensing
  • Material Aluminum alloy (maximum copper content at 0.25%) with powder polyester paint; 316 stainless steel; nickel-plated brass; tempered glass
  • Ingress Protection: Type 4X (enclosure only)
  • Display: Viewable area is 2.25”W x1.25”H (57.2mm x 31.8mm) Graphical LCD display
  • Display Language: English
  • Memory: Programming and data are protected by a non-volatile EEPROM
  • Antenna: 2.4 GHz, Hazardous Area Antenna
  • Mounting: FLEXmount™ Options
  • Weight: 7.84 lbs (Base) 9.61 lbs (Base with Sensor and Battery)
  • Communication Protocol: WirelessHART® HART 7.2 EDDL file available at www.ueonline.com/vanguard
  • Process Variables:
  • Primary Variable (PV):
  • Hydrocarbons concentration in %LEL
  • Toxic gas concentration in ppm
  • Secondary Variable (SV):
  • Temperature (°C); Not available for Hydrocarbon sensor
  • Tertiary Variable (TV):
  • Days since calibration (days)
  • Quaternary Variable (QV):
  • Battery voltage (volts)
  • Programming Access: HART hand-held communicator, or via HART modem, connected to HART terminals located in rear battery compartment or via remote access (e.g., asset management software) DTM available for PC programming
  • Calibration/Bump Test Access: Via external button on transmitter base
  • Batteries: Battery pack contains two Lithium battery cells
  • Operating Voltage: 7.2V
  • Life: 5 years based on an 8 second update rate

Product Enquiry

SSL Secure Connection