Overview:

The MPC Platinum control Series is designed to operate a steam boiler or a steam valve to provide steam outdoor reset in single-pipe and two-pipe steam heating systems. Utilizing the steam cycle concept and the outdoor temperature, the control varies the duration of the steam supply to the building in a cycle based on the outdoor temperature. Each of these options has a set of pre-configured, but adjustable settings to meet the specific needs of each building. The MPC Platinum will reduce fuel costs while maintaining a more comfortable space temperature.

The MPC Platinum offers multiple communication options. The Internet communication package offers a large group of optional sensors that can be monitored, logged, and alarm set. In addition, Heat-Timer can provide a cellular Internet connection to the control (See Internet communication ). The BACnet Communication package provides BACnet IP or BACnet MSTP compatibility in addition to the capability of communicating using other protocols when used with a Fieldserver gateway. The Modbus Communication package provide Modbus RTU Communication capability to the MPC Platinum control.

With its 80 character alphanumeric display and easy-to-use menu structure, changing settings is a snap. In addition, it incorporates Shutdown and Prove inputs for EMS capability.

Features

  • Built-In Steam Outdoor Reset
  • Can be configured for Burner or District Steam
  • Different Day and Night Adjustable outdoor temperature cutoffs
  • 4 programmable Day/Night adjustments per day
  • Auxiliary Output that can control other equipment based on a separate Built-In programmable 4 separate On/Off schedule settings per day
  • Thermal lockout does not allow the initiation of another heating cycle if the system had steam
  • BACnet IP and MSTP Communication option (field upgradeable)
  • Internet Communication option (field upgradeable)
  • Modbus RTU Communication option (field upgradeable)
  • Solid state sensors can be extended up to 500′ from the control
  • EE-Prom backup of all program settings
  • 80 Character alphanumeric display
  • EMS capable using the SHUTDOWN and PROVE inputs
  • Can link to a Multi-Mod for multiple modulating boilers
  • Additional Output relays to control other equipment based on the MPC Platinum cycle operation
  • Network input allows the MPC Platinum to connect to multiple sensors (MIG Sensors, Neuron Sensors, Wireless Sensors, Water Meter, Gas Meter, Oil Level, Smoke Alarm) using the Internet to monitor and fine tune its operation
  • Optional Remote Communication using the Internet, BACnet, or Modbus. You’ll be able to view status, change settings as well as analyze performance from virtually anywhere
  • MPC Platinum is NYC DEP Approved (DEE #42-04)