The model CGS sensor when used with the CTX10 is a catalytic combustible gas detector, provides continuous monitoring of combustible hydrocarbon gas and combustible hydrogen gas concentrations in the range of 0% LFL to 100% LFL. The CTX10 is third-party performance approved for methane and propane gases.

Features

  • Onboard magnetic calibration/reset switch for non-intrusive calibration capability
  • Compatible with constant current Det-Tronics catalytic sensors
  • Direct field replacement for Det-Tronics Model 505 Transmitters
  • Current level indicates fault condition and calibrate mode
  • Sensor sensitivity check
  • Suitable for use in a wide variety of combustible gas detection applications
  • Available in 316 stainless steel and black epoxy aluminum (shown)
  • Explosion-proof junction box available in aluminum or stainless steel

Technical Specifications

  • INPUT VOLTAGE—
  • 24 Vdc Nominal, Operating range of 18 - 30 Vdc Ripple cannot exceed 0.5 Volts P-P
  • POWER CONSUMPTION—
  • 4.0 watts maximum
  • PEAK STARTUP CURRENT—
  • Less than 0.5 ampere for < 0.2 second at 10 Vdc input, and less than 0.2 ampere for < 0.2 second at 24 Vdc input.
  • OUTPUT CURRENT—
  • Linear 4 to 20 mA
  • CURRENT LEVEL—
  • Calibration Fault: 1.6 mA
  • Other Faults: 1.0 mA
  • Calibration Mode: 2.0/2.2 mA in Infiniti mode, 3.4 mA in 505 mode
  • Three LEDs provide the following visual annunciation at the device:

Color

Function/Indication

Green

Power

Yellow

Calibration, Faults

Blue

End of life